(a) Generally. Under this article, this method requires the designer or architect to follow the construction requirements for all exterior façade elements as listed in the tables below.

Table 22-1. Residential construction requirements in the NID, NIBA, and LDN 551

Façade Element

Minimum Requirement

Exterior walls

Structural

2" by 4" wood or metal studs

Insulation

R-15 bat insulation or full cavity fill

Interior gypsum

Blown cellulose

Exterior applications

1-layer of ½" or ⅝" gypsum

7/16" OSB or plywood and stucco, siding, brick or stone

Basement walls

Basements are excluded, as long as basement windows and sliding glass doors have minimum STC ratings of 30.

Exterior floors

Normal construction, except for full joist fill insulation

Roof and exterior ceilings

Minimum attic insulation shall be R-38. Vaulted roof/ceiling structures are allowed, coffered ceilings are acceptable. For vaulted ceilings the minimum joist or truss depth is 14 inches. Use of vaulted ceilings increases required STC rating of windows above those listed.

Doors

Exterior swing doors

Solid core doors with jamb seals and sweeps, glazing in doors shall have minimum STC rating of 30

Sliding glass doors

Minimum STC rating of 30

Windows

Minimum STC rating of 30

HVAC and appliance venting

Shall be as specified in sec. 22-433

1Minimum 25 OITL decibels

2Minimum 30 OITL decibels

Table 22-2. Residential construction requirements in SNID and LDN 65

Façade Element

Minimum Requirement

Exterior walls

Structural

2" by 6" wood or metal studs

Insulation

R-19 BAT insulation or full cavity fill blown cellulose

Interior gypsum

2-layers of ½" or ⅝" gypsum

Exterior applications

2-layers of ½" or ⅝" gypsum

7/16" OSB or plywood and stucco, siding, brick or stone

Basement walls

Basements are excluded, as long as basement windows and sliding glass doors have minimum STC ratings of 34.

Exterior floors

Normal construction, except for full joist fill insulation

Roof and exterior ceilings

Minimum attic insulation shall be R-38. Joist type vaulted roof/ceiling structures are not allowed, coffered ceilings are acceptable. Truss type vaulted ceilings are allowed and shall have a minimum truss depth of 36". Use of vaulted ceilings increases required STC rating of windows above those listed.

Doors

Exterior swing doors

Solid core doors with jamb seals and sweeps, glazing in doors shall have minimum STC rating of 34

Sliding glass doors

Minimum STC rating of 34

Windows

Minimum STC rating of 34

HVAC and appliance venting

Shall be as specified in sec. 22-433

1Minimum 25 OITL decibels

2Minimum 30 OITL decibels

Table 22-3. Commercial construction requirements in LDN 651

Façade Element

Minimum Requirement

Exterior walls

Typical commercial construction

Roof and exterior ceilings

Typical commercial roof/ceiling construction

Doors

Typical commercial doors

Windows

If window area in a specific room is less than 20% of the total area minimum STC rating of 28, if window area in a specific room is greater than 20% of the total area minimum STC rating of 32

HVAC and appliance venting

None

1Minimum 25 OITL decibels

Table 22-4. Commercial and residential construction requirements in the CANA2

Façade Element

Minimum Requirement

Exterior walls

Typical commercial construction

Roof and exterior ceilings

Typical commercial roof/ceiling construction

Doors

Typical commercial doors

Windows

If window area in a specific room is less than 20% of the total area minimum STC rating of 30, if window area in a specific room is greater than 20% of the total area minimum STC rating of 32

HVAC and appliance venting

None

2Minimum 30 OITL decibels

(d) Construction. All exterior walls, roofs and exposed floors shall be of airtight construction. All nonlap joints shall be grouted or caulked airtight with a nonhardening, nonshrinking sealant installed in accordance with manufacturer's specifications. Any penetrations of exterior walls or roofs by pipes, ducts or conduits shall be sealed airtight as required for joints. Door and window openings in exterior walls shall be flashed all around with an approved vapor barrier and sealed to prevent air infiltration. Sill sealant shall be used to prevent air infiltration at all base plates of exterior walls. Attic and crawl space vents shall not exceed minimums specified by ordinance. Crawl space vents shall be baffled as shown in figure 22-1. See section 22-432 for building mechanical systems. (Ord. No. 2011-07, § 4, 4-11-2011; Ord. No. 2007-49, § 17, 8-27-2007; Ord. No. 2006-78, § 1(Exh. A), 1-8-2007)